| Boiler Model Number |
Oil Input² |
Gas Input³ MBH |
Gross Output MBH |
Net I=B=R Ratings¹ |
Oil |
Gas |
Boiler H.P. |
Water Content, gal |
Furnace Volume, cuft |
Water Working Weight, lbs. |
Heating Surface, sqft |
| GPH |
MBH |
Steam, sqft |
Water², MBH |
Steam³, MBH |
Combustion Efficiency5, % |
Thermal Efficiency5, % |
Combustion Efficiency5, % |
Thermal Efficiency5, % |
Water |
Steam |
TCII-04
TCII-05
TCII-06 |
7.9
10.2
12.2 |
1,106
1,428
1,708 |
1,143
1,458
1,773 |
931
1,194
1,458 |
2,908
3,733
4,625 |
810
1,038
1,268 |
698
896
1,110 |
86.2
86.2
86.1 |
83.9
84.4
84.8 |
83.6
83.6
83.5 |
81.4
81.9
82.2 |
28
36
44 |
123.4
150.3
177.2 |
103.8
125.8
147.8 |
12.04
16.14
20.24 |
4,215
5,038
5,861 |
81.2
105.3
129.4 |
TCII-07
TCII-08
TCII-09 |
14.4
16.6
18.8 |
2,016
2,324
2,632 |
2,088
2,403
2,718 |
1,722
1,985
2,249 |
5,542
6,421
7,275 |
1,497
1,726
1,956 |
1,330
1,541
1,745 |
86.1
86.1
86.1 |
85.0
85.2
85.3 |
83.5
83.5
83.5 |
82.5
82.6
82.7 |
51
59
67 |
204.1
231.0
257.9 |
169.8
191.8
213.8 |
24.34
28.44
32.54 |
6,684
7,507
8,331 |
153.5
177.6
201.7 |
TCII-10
TCII-11
TCII-12 |
21.0
23.0
25.5 |
2,940
3,220
3,570 |
3,033
3,348
3,663 |
2,513
2,776
3,040 |
8,129
8,979
9,833 |
2,185
2,414
2,643 |
1,951
2,155
2,360 |
86.1
86.0
86.0 |
85.4
85.5
85.6 |
83.5
83.5
83.5 |
82.8
82.9
83.0 |
75
83
91 |
284.8
311.7
338.6 |
235.8
257.8
279.8 |
36.64
40.74
44.84 |
9,169
9,992
10,815 |
225.8
249.9
274.0 |
TCII-13
TCII-14
TCII-15 |
27.5
29.5
32.0 |
3,850
4,130
4,480 |
3,978
4,293
4,608 |
3,304
3,567
3,851 |
10,688
11,538
12,392 |
2,873
3,102
3,331 |
2,565
2,769
2,974 |
86.0
86.0
86.0 |
85.6
85.7
85.7 |
83.5
83.5
83.4 |
83.0
83.1
83.1 |
99
107
114 |
365.5
392.4
419.3 |
301.8
323.8
345.8 |
48.94
53.04
57.14 |
11,649
12,467
13,511 |
289.1
322.2
346.3 |
TCII-16
TCII-17
TCII-18 |
34.0
36.5
38.5 |
4,760
5,110
5,390 |
4,923
5,238
5,553 |
4,095
4,358
4,622 |
13,246
14,100
14,954 |
3,561
3,790
4,019 |
3,179
3,384
3,589 |
86.0
86.0
86.0 |
85.7
85.8
85.8 |
83.4
83.4
83.4 |
83.2
83.2
83.2 |
122
130
138 |
446.2
473.1
500.0 |
367.8
389.8
411.8 |
61.24
65.34
69.44 |
14,375
15,239
16,103 |
370.4
394.5
418.6 |
1 Net I=B=R Water Ratings are based on allowance of 1.15. Net I=B=R Ratings for steam boilers are based on piping and pick-up factor as follows: 4 and 5 section = 1.333, 6 and 7 section = 1.305, 8 section and larger = 1.288.
2 Light oil having a heat content of 140,000 BTU/Gal.
3 Gas having a heat content of 1,000 BTU/Cu. Ft., 0.60 specific gravity.
4 Consult factory before selecting a boiler for installation having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
5 Combustion and thermal efficiency determined in accordance with BTS 2000 Testing Standard for Heating Boilers.
Don't see the information you need? See the "Related Documents" tab for product resource downloads.